GEORGE DONNELLY TESTING & INSPECTIONS
(501) 915-0626
Calcium Chloride v. In-situ Relative
Humidity

Most U.S. producers of floor coverings, adhesives and resinous coatings have
historically looked
to the calcium chloride method of testing concrete slabs to determine dryness and
suitability for the installation of their products. The American Society for
Testing and Materials (ASTM) has written a standard for the use of anhydrous
calcium chloride when testing dryness of concrete. The standard is also known as
ASTM F-1869-04. Some floor covering manufacturers are now suggesting the use of
in-situ relative humidity data as the preferred method of determining concrete
dryness. ASTM has also published a standard test method for the use of in-situ
relative humidity probes, the test designation is ASTM F-2170-02. This test method involves measuring relative humidity
levels inside of the concrete slab and finds it's basis in testing commonly
performed in Europe. ASTM F-710 offers recommendations regarding the
suitability of a concrete slab for the installation of resilient floor coverings
based on results achieved by these test methods. This standard states that
moisture vapor emission, per ASTM F 1869, should not exceed 3 pounds per 1,000
square feet per 24 hours, unless otherwise specified by the flooring or adhesive
manufacturer. The standard continues by stating that relative humidity inside of
a
concrete slab should not exceed 75%, per ASTM F 2170, unless otherwise specified
by the flooring or adhesive manufacturer.
This agency is now performing tests by both methods and while neither method
can offer a 100% guarantee of long-term successful floor covering installation the
following is offered for your consideration.

Before discussing the individual test methods, it is important to note that
in our opinion, all existing test methods are capable of being
"fooled" under certain conditions. In example, when a very porous
concrete, or a concrete mix design with a high water/cement ratio, is placed
without the protection of an effective sub-slab vapor retarder, concrete
moisture content and vapor emission can vary dramatically with seasons or other
changing conditions. There have been studies published that show an effect of
installing floor coverings or coatings with limited permeability is that of
increasing moisture content in concrete, when a sub-slab moisture source is available. In
example, we regularly see situations in which the new tenant of a building wanted
to increase office or production space into areas that were designed to be
warehouse floor. Inexperienced people tested the floor with a calcium chloride
test kit, found the results met the criteria required by the selected
floor covering manufacturer and recommended that installation of materials
proceed. Soon after installation, the flooring or its adhesive system failed and
new tests were ordered. The new tests reveal moisture vapor emission levels far
higher than the original test results and the inevitable finger pointing ensued.
Typically, the concrete surface of an open warehouse floor will become sufficiently
dry and reveal moisture vapor emission levels low enough to pass the
requirements of a floor covering manufacturer. However, once covered, moisture
content in the concrete may begin to rise and can cause a failure of the floor
covering system. We often see this same issue in residential projects when
carpet and pad are replaced with sheet vinyl or wood flooring products. Although
we have not yet seen this difficulty when testing with in-situ relative humidity
probes, there should always be concern when covering or coating concrete that is
not protected by an effective sub-slab vapor retarding membrane. Some floor
covering manufacturers specifically require the existence of a sub-slab vapor
retarder beneath
slab-on-grade concrete when their materials are to be installed.
Calcium Chloride or "Moisture Dome" Tests -
Pro -
1. Results of calcium chloride testing are accepted by most U.S.
manufacturers of floor covering, adhesive and resinous coating products as the
benchmark for concrete dryness and suitability for the installation of their
products. As noted above ASTM F-710 contains the statement that concrete can be
considered suitably dry when vapor emission does not exceed 3 pounds per 1,000
square feet per 24 hours, when tested in accordance with test method ASTM F
1869-04.
2. Testing is relatively easy to perform, no major investment in
equipment is required.
Con -
1. The subject building must be acclimated at or near the temperature and
relative humidity levels anticipated during occupancy or use. This is often a
difficult requirement to meet on a new construction project. If the HVAC system
is not operational at the time of testing a recording hygrometer should be
employed to monitor and record ambient temperature and relative humidity levels
for comparison to intended occupancy conditions. Significant variance between
the test environment and intended use environment should cause test data to be
questioned.
2. Calcium chloride tests reflect moisture vapor emission from the surface of
the concrete. It has been suggested that the test reflects moisture in the top
1/4 to 1/2 inch of the slab's thickness. If ambient environmental conditions immediately preceding testing
have been extremely dry or wet, the concrete surface may be affected and test
results may be skewed accordingly.
3. Testing on an open, or breathing, concrete surface may not reflect
moisture deep within or directly below the concrete slab. Once covered by low
permeability floor coverings, concrete moisture content will equalize within the
thickness of the slab. This may mean that a greater volume of moisture will be
present at the floor covering/concrete interface after installation is completed
than was originally
anticipated. See the attached article When 3 lbs is not 3 lbs.pdf
4. "Home-made" calcium chloride test kits are being used and in
some cases by very reputable labs. Some of these kits do not meet the apparatus
requirements of ASTM F-1869-04 and are delivering questionable results.
5. Too many tests are being set without floor preparation as required by ASTM
F-1869. Surface contaminants and residue from paint, adhesive, curing or parting compounds can reduce vapor emission at the test site and produce
inaccurate test results. Some penetrating parting compounds (tilt-up
construction) or penetrating cure and seal products are difficult to detect and
impossible to remove. They restrict moisture release and result in reduced vapor
emission test results. It is our experience that some of these products will
slowly degrade leading to latent moisture release from the concrete and eventual
floor covering system failure.
In-situ Relative Humidity Testing
Pro -
1. It is our field experience that testing slab-on-grade concrete offers
results, which are less impacted by ambient temperature and relative humidity
conditions than calcium chloride type tests. Thus generating meaningful data under conditions
that may not be acceptable for calcium chloride testing. Concrete slabs in
contact with the earth are a heat sink and their internal temperature is
affected by both the sub-slab soil temperature and by the temperature of the air
space above. Whereas the internal temperature of suspended concrete will be
driven by temperature of the air space above and below the slab. It must be
noted that ASTM F2170 states that slabs, which are to be tested should be
"at service temperature and the occupied air space above the floor slab
shall be at service temperature and service relative humidity for at least 48
hours before making relative humidity measurements in the concrete slab."
2. Testing performed at multiple depths permits a testing agency to develop a
profile of moisture conditions through the thickness of a concrete slab. This
information permits the user to make a more informed decision regarding the
installation of floor coverings or the need to consider other alternatives.
3. Test results appear to be less impacted by the type of, or lack of, floor
coverings in place prior to testing.
Con -
1. As of this writing only a few U.S. manufacturers of floor coverings,
adhesives and resinous coatings have published recommendations or guidelines for
the installation of their products based on in-situ relative humidity test results.
Most resilient floor covering manufacturers recognize ASTM F-710-03, which
states in Section 5.2.2 "In accordance with Test Method ASTM F
2170, the relative humidity in a concrete floor slab shall not exceed 75% at the
time of testing, unless otherwise specified by the flooring or adhesive
manufacturer."
2. Testing requires a substantial investment in tools and equipment, which will limit
the number of agencies performing these tests.
3. We are seeing data developed by testing agencies that are not following
ASTM F 2170 protocol, particularly with regard to acclimation of the test hole
and test probe. Without temperature equilibration of the test site and test
apparatus, the data generated may be skewed high or low relative to the
direction of inequity, thus rendering data collected misleading or meaningless.
In a recent article Vaisala, Inc. made the following statements "A Relative
Humidity measurement can vary significantly when there is a difference in
temperature between the air (concrete) being measured and the measurement probe.
For example, if the probe temperature is 1º C lower than the air (concrete)
temperature, you would increase your error by about 3% RH". If someone
takes a test probe from a hot or cold automobile and drops it into a test hole
for only a few minutes the error factor can becomes enormous and the data
collected is meaningless.
_______________
It is the opinion of this agency that a combination of these tests, performed
concurrently in a subject building, offers the greatest depth of data and
confidence in decisions that may be made based on such data. When a single
test is specified, it is our opinion that the calcium chloride test is best used
as a forensic tool in failure investigations and in-situ relative humidity tests
are the best pre-installation predictor of potential moisture related floor covering installation
failures. We welcome comments regarding
this essay from any and all interested parties. You may call us at (501)
915-0626 or send an e-mail to info@moisturetesting.com
Thank you for visiting this site and your interest in the subject matter.
Revised 7/07
|